Description
Test the electrical safety of your installations. Discover our new CA 6133 electrical installation tester.
Earth measurement by stake and loop
methods
> Continuity measurement at 0.2A
> Isolation test
> RCD test: tripping current and time
> Automatic test sequences
> Storage of the tests in memory
> ANDROID application for report
generation
> Power supply by mains-rechargeable
batteries: USB socket or vehicle
cigarette lighter
CA 6133
CONTINUITY / RESISTANCE
Range / Resolution / Accuracy
0.00 to 9.99 Ω — Cable compensation up to 5 Ω;
I >= 200 mA / 0.01 Ω / ± (2 % R + 2 cts)
Range / Resolution / Accuracy
1 to 9,999 Ω • 10.00 to 99.99 kΩ / 1 Ω • 10 Ω /
± (1 % R + 5 cts)
INSULATION
Rated voltage Utest: 250 V / 500 V / 1,000 V
Range / Resolution / Accuracy
0.01 to 999.9 MΩ / 10 kΩ •
100 kΩ / ± (3 % R + 3 cts)
Short-circuit current ≤ 3 mA
3P EARTH
Range / Resolution / Accuracy
0.50 – 99.99 Ω /0.01 Ω/±(2 % R + 10 cts)
100.0 to 999.9 Ω /0,1 Ω/±(2 % R + 5 cts)
1,000 to 2,000 Ω /1 Ω/±(2 % R + 5 cts)
(Zs (L-PE) and Zi (L-N or L-L) LOOP IMPEDANCE
Installation voltage / Frequency 90 to 550 V / 45 to 65 Hz
High current mode with TRIP: Zs (L-PE)
& Zi (L-N or L-L)
Range / Resolution / Accuracy
300 mA measurement current; 0.1 to 0.9 Ω •
1.0 to 399.9 Ω / 0.1 Ω / ±(2 cts) •
±(5 % R* + 2 cts)
NO TRIP mode (Zs (L-PE) only)
Measurement current: 12 mA • 1 to 19 Ω • 20 to 39 Ω
40 to 2,000 Ω / 1 Ω / ±(2 cts) • ±(15 % R + 3 cts) •
± (5 % R + 2 cts)
Calculation of Ik short-circuit current
(PFC (Zs)) , (I Sc PSCC (Zi))
1 to 999 A, 1 to 9,999 A
TYPE AC and A RCDs
Installation voltage / Frequency 90 to 450 V ; 45 to 65 Hz
I∆n 30 mA – 100 mA – 300 mA – 500 mA – 650 mA
NO TRIP test 300 ms
Ramp mode (30 mA) 12 mA (Uf) / 0.3 to 1.06 x IΔn per step of 3.3 % x IΔn
Trip time measurement: Range /
Resolution / Accuracy
Pulse: 5 to 300 ms / 0.1 ms / ± 2 ms
Automatic test sequence RCD, Loop-RCD-Isolation
OTHER MEASUREMENTS
Current via MN73A clamp
2A range: 10.0 mA to 2,400 mA,
200 A range: 1.00 to 200 A
Voltage
Range / Resolution / Accuracy
2.0 to 550.0 VAC / 0.1 V / ± (1%R+2cts) ;
0.0 to 800.0 VDC / 0.1 V / ± (1%R+2cts)
Frequency
Range / Resolution / Accuracy
30.0 to 999.9 Hz / 0.1 Hz / ±(0.1 % R + 1 ct)
Voltage > 2V
Phase rotation 45 to 550 V / 45 to 65 Hz
GENERAL SPECIFICATIONS
Display 231-segment LCD with blue backlighting
Storage / Communication 30 sites x 99 tests / Bluetooth Class 1; range > 10m
Power supply / battery life
6 NiMH mains-rechargeable batteries
< 6 hrs , USB or cigarette lighter/ 1,700 x 1 Ω
continuity measurements
Dimensions / weight 223 x 126 x 70 mm / 700 g approx.
Ingress protection / EMC IP 54; IK 04 / EMC: IEC 61326-1
Electrical safety
IEC 61010-1 ; IEC 61010-2-030 ;
IEC 61010-2-034, 600V CAT III, 300V CAT II
(charger)/ Compliant with IEC 61557
parts 1,2,3,4,5,6,7,10